Has a rated capacity of 30 Amps at 120 VAC and is suitable for a 30 Amp Utility Power Cord and a Generator of up to 3.6 KVA capacity.
Uses a heavy duty Double Pole Double Throw (DPDT) relay for switching both the Line and Neutral.
Can be installed on the line side of the main breaker panel allowing switching of the entire load or on the load side to only switch dedicated circuits.
DIP Switch select to enable a time delay when transferring to a generator.
Comes with a standard North American power cord for convenient connection to 15 Amp NEMA5-15R receptacles on a generator or an inverter with up to 1800 VA capacity (Replace this cord with 30 Amp cord if full 30 Amp capacity is required).
Input / output voltage: 120 VAC, 60 Hz.
Input / output current: 30 A.
Battery charger receptacle: Dual NEMA5-15R, 5 A max, 12 A continuous, Fused at 15 A.
Knockouts: for 1" and ¾".
Maximum operatin g time of the relay : 25 msec.
Delay time for generator warm up: 20 sec + / - 5 sec.
Enabling / disabling of delay time:Yes. With DIP switch SW1, Delay enabled: OFF (1), Delay disabled: ON.